HGMSZ  

Search:

Up ]


Halogen Gas Monitor Single Zone

The Bacharach HGMSZ (Halogen Gas Monitor Single Zone) is designed for continuous single-point monitoring of CFC, HFC, HCFC and Halon refrigerant gases. The HGMSZ displays the type of gas being monitored, along with displaying both the current gas level and the peak gas level detected on its front panel LCD. The instrument retains a log of previous readings that can be easily accessed for analysis.

An internal audible alarm and front panel indicators are provided to signal alarm and fault conditions, and relay contacts can be used to trigger external alarm devices in the event of a system fault, or if a leak (small), spill (medium), or evacuation (large) level of gas is detected. The system also includes a 4–20 mA current loop interface that can be connected to remote monitoring equipment.

Features

  • Easily complies with ASHRAE 15 requirements with a low-cost investment
  • Eliminate false alarms with use of non-dispersive IR source and sample draw system
  • Capable of detecting 30 of the most commonly used refrigerants and halogen gases
  • Measure all gases up to 10,000 ppm with a sensitivity of 1 ppm
  • Monitors a single zone located up to 50 feet from unit
  • Logging feature enables 200 gas readings to be stored
  • Three gas alarm levels that can be individually set
  • Bolt-in, bolt-out internal components so the unit never leaves the wall
  • Two-year warranty

Specifications

  • Refrigerant Library:
    R‑11, R‑12, R‑21, R‑22, R‑23, R‑113, R‑114, R‑123, R‑124, R‑134a, R‑227, R‑236FA, R‑401a, R‑402a, R‑402b, R‑404a, R‑407a, R‑407c, R‑408a, R‑409a, R‑410a, R‑500, R‑502, R‑503, R‑507, R‑508b, H‑1211, H‑1301, H‑2404, N‑1230
  • Measuring Range:  All gases 0 to 10,000 ppm
  • Input:  Dedicated single zone
  • Output Signals:  4 SPDT, 5 Amp, 240 VAC relays; digital display; and a 4–20 mA DC current loop output
  • Detector Type:  Single pass, non-dispersive infrared
  • Sensitivity:  All gases 1 ppm
  • Accuracy:  All gases ±10 ppm from 0 to 100 ppm, ±10% of reading from 100 to 10,000 ppm
  • Front Panel Indicators:

    MONITOR ON – Green light ON when the unit is operating normally, or flashing during warm-up
    SYSTEM FAULT – Yellow light ON when there is a system fault
    ALARM – Red light ON when the gas level is above an alarm setting

  • Response Time:  9 to 30 seconds, depending on tube length and gas concentration

  • Max. Monitoring Distance:  Up to 50 feet from measuring point to monitor
  • Operating Temperature:  32 to 122°F (0 to 50°C)
  • Humidity:  5 to 90% RH, non-condensing
  • Altitude Limit:  2000 Meters
  • Power:  100–240 VAC, 50/60 Hz, 15 Watts
  • Size/Weight:  14"H x 18"W x 4.7"D / 7 lbs
  • Certification:  UL 61010A-1, CSA 22.2, CE Mark

Ordering Information

Part Number Description
3015-4200 HGMSZ (Halogen Gas Monitor Single Zone)
304-2743 Sample / Exhaust / Purge Line tubing
3015-3420 Termination Filter
3015-4121 120 VAC surge protector
3015-4122 220 VAC surge protector
3015-4123 4–20 mA surge protector
3015-3069 120 VAC external visual alarm
3015-3070 120 VAC external audible alarm
3015-3076 120 VAC external audible / visual alarm

Additional Product Information

(1824K) Data Sheet
(2500K) Instruction Manual
(632K) IR Bench Replacement Instructions

Home  Top