MULTI-ZONE
Fixed Refrigerant Gas Monitors
•
|
HGM300 / RDM-800: CFC, HFC, HCFC and Halon
Gases
|
•
|
AGM300 / ADM-800: Ammonia Gas
|
The HGM300 / AGM300 Multi-Zone Refrigerant Monitor, and the RDM-800
/ ADM-800 Remote
Display Module combine to provide a multiple refrigerant gas and multiple
area monitoring system for low level continuous monitoring of CFC, HCFC, HFC,
and ammonia refrigerant gases. |
Features
- Select refrigerants to be
measured - point by point
- Eliminate false alarms with use
of non-dispersive IR source and sample draw system
- Measure all gases up to 10,000
ppm with a sensitivity of 1 ppm
- Sample points locate up to 500
feet from unit
- Remotely interrogate,
acknowledge alarms
- Quick field expansion from 4 to
16 sampling zones
- Bolt-in, bolt-out internal
components so the unit never leaves the wall
- Full two-way communication via
RS-458
- RS-232 port for local / modem
communication
- Split-architecture design keeps
your investment to a minimum
- UL and CE approved
- Two-year warranty

Specifications
HGM300 / AGM300 - Multiple refrigerant gas and
multiple area monitor. May be used "stand alone" or combined with other HGM300
/AGM300
units reporting to the RDM-800 / ADM-800 remote display.
- Refrigerants:
- HGM300
CFC: R11, R12, R113, R114, R502, R404a (HP62), R407a, R407c (AC9000), R134a,
R410a (AZ20), R507
(AZ50), R508b (SUVA95)
HCFC: R22, R123, R124, R500, R503, R401a
(MP39), R402a (HP80), R40b
(HP81), R408a, R409a, R23
HALON: 1301
- AGM300
R-717 (Ammonia)
- Measuring Range:
- HGM300: All gases 0 to 10,000 ppm
- AGM300: 25 to 10,000 ppm
- Inputs: 4 points standard, expandable to 16 points in 4 point
increments
- Output Signal: 4–20 mA DC (optional)
- Detector Type: Non-dispersive infrared
- Sensitivity: All gases 1 ppm
- Accuracy: All gases ±10 ppm from 0 to 100 ppm, ±10% of reading from
100 to 10,000 ppm
- Front Panel Display:
- Green LED indicates when unit is operating properly
- Red LED indicates when any monitored point is above its alarm setting
- Yellow LED indicates a clogged sample line or other system fault
- Response Time: 5 to 120 seconds, depending on tube length and gas
concentration
- Max. Monitoring Distance: Up to 500 feet from measuring point to
monitor
- Operating Temperature: 32 to 113 °F (0
to 45 °C)
- Power: 120/240 VAC, 50/60 Hz
- Size/Weight: 17" x 12" x 5.5" / 15 lbs (may be wall or rack
mounted)
RDM-800 / ADM-800 - Display Module provides remote programming,
interrogation and display functionality to support the HGM300 / ADM300 Refrigerant
Monitor.
- Inputs: Accepts from one to four inputs via RS-485 from up to four
HGM300 / AGM300 Refrigerant Monitors
- Display: Backlit LCD displays the measured point in ppm
- Trend Mode / Data logging: User may select a graphical display of
the ppm trend for any measured point (100 data entries per point)
- Alarm Indications: Channel display flashes, red light flashes,
alarm signal sent via RS-485
- Input Fault Indication: Yellow light flashes and the LCD indicates
location of input fault
- Maximum Distance from Monitor: Maximum of 4,875 wiring feet from
the furthest monitoring unit to the display module
- Operating Temperature: 32 to 113 °F (0
to 45 °C)
- Power: 120/230 VAC, 50/60 Hz
- Size/Weight: 11" x 10" x 3" / 5 lbs (wall mounted)

Software
HGM300 PC Software Download
AGM300 PC Software Download

Additional Product Information
(305K) Data Sheet
(10348K) AGM300/ADM-800 Full Instruction Manual
(1667K) HGM300/RDM-800 Mini Instruction Manual
(7370K) HGM300/RDM-800 Full Instruction Manual
(1007K) HGM300 IR Bench Replacement Instructions
(1007K) AGM300 IR Bench Replacement Instructions
(153K) PC Software Manual
(2300K) Adding Additional Manifolds |